Galaxy VS UPS 30kW 400V for up to 4 internal 9Ah smart modular battery strings, Start-up 5×8

GVSUPS30K0B4HS Product picture Schneider Electric

Overview
Presentation
Highly efficient, easy-to-deploy 30kW, 400V 3-phase UPS that brings best-in-class power protection and low total cost of ownership to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. This UPS is for up to 4 smart modular high capacity battery strings, but is supplied without batteries, so you can easily customize the battery runtime. Includes 5×8 start-up service.
Lead time
Usually Ships within 2 Weeks
General
provided equipment
Dust filter
Installation manual
Integrated network management
Start-up service
EcoStruxure Ready
Number of power module free slots
0
Number of power module filled slots
0
redundant
No
UPS size
WS
Physical
surface finish
Gloss level 85%
colour
White (RAL 9003)
depth
84.7 cm
height
148.5 cm
mounting preference
No preference
net weight
200 kg
mounting mode
Not rack-mountable
two post mountable
0
USB compatible
No
width
52.1 cm
Input
network frequency
40…70 Hz
input voltage limits
340…460 V 400 V
inputvolt_other
380 V
415 V
maximum input current
54 A
max short time withstand current
65 kA
input harmonic distortion
Less than 3 % for full load
input voltage
400 V 3 phases
load power factor
From 0.7 leading to 0.7 lagging without any derating
cos phi
0.99
Output
rated power in W
30000 W
Maximum configurable power in W
30000 W
harmonic distortion
Less than 3 %
output frequency
50 Hz sync to mains
60 Hz sync to mains
outputvolt_other
380 V
415 V
crest factor
2.5
UPS type
Double conversion online
Wave type
Sine wave
output voltage tolerance
+/- 5% after 2ms
+/-1% after 50ms
output harmonic distortion
< 1% linear load and < 3% non-linear load
output overload operation
10 minutes at 125% and 60 seconds at 150%
bypass type
Built-in static bypass
curve equation
Efficiency
curve fixed loss
0.008
curve load maximum
100 %
curve load minimum
1 %
curve proportional loss
0.0194
curve square loss
0.0056
curve X-axis maximum
100 %
curve test cond ID
Curve fit to measured efficiency data. All measurements taken in normal operating mode, at typical environmental conditions, with 400V 50Hz input and 400V 50Hz balanced resistive load (PF = 1.0) output.
curve X-axis minimum
0 %
curve X-axis title
Load
curve X-axis units
Percentage
curve Y-axis maximum
100 %
curve Y-axis minimum
50 %
curve Y-axis title
Efficiency
curve Y-axis units
Percentage
graph display
1
output voltage
400 V 3 phases
Maximum configurable power in VA
30000 VA
rated power in VA
30000 VA
Conformance
standards
IEC 62040-1-1
IEC 62040-2
OSHPD
Environmental
ambient air temperature for operation
0…40 °C
relative humidity
0…95 % non-condensing
operating altitude
0…3300 ft
ambient air temperature for storage
-15…40 °C
Storage Relative Humidity
Non-condensing 10…80 %
storage altitude
0.00…3048.00 m
acoustic level
61 dBA
heat dissipation
3395 Btu/h
show note OP temperature
No
IP degree of protection
IP20
Batteries & Runtime
battery type
VRLA
number of battery filled slots
0
number of battery free slots
0
liquid value
0
battery voltage
480 V
discharge battery voltage
384 V
max current discharge
81 A
battery curve
B
Battery power in VAH
0 VAh runtime
extended runtime
0
Communications & Management
control panel
Touch screen LCD user interface
alarm
Audible and visible alarms prioritized by severity
Packing Units
Package 1 Weight
200 kg
Package 1 Height
168 cm
Package 1 width
64 cm
Package 1 Length
99 cm
Contractual warranty
Warranty
1 year on-site repair or replace with factory authorized Start-Up