[titles text=”T3VyJTIwVXNlcnM=” type=”h2″]






[titles text=”T3VyJTIwVXNlcnM=” type=”h2″]
Presentation |
Highly efficient, easy-to-deploy 20kW, 400V 3-phase uninterruptible power supply (UPS) that brings best-in-class power protection to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. Compact design, high-density technology and modular architecture keep total cost of ownership low and operational efficiency at the highest levels. Galaxy VS reduces your energy losses by up to 66% with the patented ECOnversion mode – reaching up to 99% efficiency levels and delivering more energy savings than even our industry-leading 97% efficiency in normal operating mode. The UPS is EcoStruxure-ready to give you peace of mind with cloud-based remote monitoring and management via your smartphone. Includes 5×8 start-up service. For battery runtime details, see the runtime charts published under the Documents tab.
|
|
---|---|---|
Lead time |
Usually Ships within 2 Weeks
|
provided equipment |
Dust filter
Installation guide Integrated network management Power modules ship installed Start-up service Top and bottom cable entry |
|
---|---|---|
bypass voltage tolerance |
+/- 10 %
|
|
max bypass input current |
32 A
|
|
Number of power module free slots |
0
|
|
Number of power module filled slots |
0
|
|
redundant |
No
|
|
UPS size |
WS
|
surface finish |
Gloss level 85%
|
|
---|---|---|
colour |
White (RAL 9003)
|
|
depth |
84.7 cm
|
|
height |
148.5 cm
|
|
mounting preference |
No preference
|
|
net weight |
210 kg
|
|
mounting mode |
Not rack-mountable
|
|
two post mountable |
0
|
|
USB compatible |
No
|
|
width |
52.1 cm
|
network frequency |
40…70 Hz
|
|
---|---|---|
number of input connectors |
1 hard wire 4-wire (3P + E)
1 hard wire 5-wire (3P + N + E) |
|
input voltage limits |
340…460 V 400 V
|
|
inputvolt_other |
380 V
415 V |
|
maximum input current |
37 A
|
|
max short time withstand current |
65 kA
|
|
input harmonic distortion |
Less than 3 % for full load
|
|
input voltage |
400 V 3 phases
|
|
load power factor |
From 0.7 leading to 0.7 lagging without any derating
|
|
cos phi |
0.99
|
rated power in W |
20000 W
|
|
---|---|---|
Maximum configurable power in W |
20000 W
|
|
harmonic distortion |
Less than 3 %
|
|
output frequency |
50 Hz sync to mains
60 Hz sync to mains 50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised 60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised |
|
outputvolt_other |
380 V
415 V |
|
crest factor |
2.5
|
|
UPS type |
Double conversion online
|
|
Wave type |
Sine wave
|
|
output connector type |
Hard wire 5-wire (3P + N + E) 1
|
|
output voltage tolerance |
+/-1% after 50ms
|
|
output harmonic distortion |
< 1% linear load and < 3% non-linear load
|
|
output overload operation |
10 minutes at 125% and 60 seconds at 150%
|
|
bypass type |
Built-in static bypass
|
|
curve equation |
Efficiency
|
|
curve fixed loss |
0.0091
|
|
curve load maximum |
100 %
|
|
curve load minimum |
1 %
|
|
curve proportional loss |
0.0224
|
|
curve square loss |
0.0005
|
|
curve X-axis maximum |
100 %
|
|
curve test cond ID |
Curve fit to measured efficiency data. All measurements taken in normal operating mode, at typical environmental conditions, with 400V 50Hz input and 400V 50Hz balanced resistive load (PF = 1.0) output.
|
|
curve X-axis minimum |
0 %
|
|
curve X-axis title |
Load
|
|
curve X-axis units |
Percentage
|
|
curve Y-axis maximum |
100 %
|
|
curve Y-axis minimum |
50 %
|
|
curve Y-axis title |
Efficiency
|
|
curve Y-axis units |
Percentage
|
|
graph display |
1
|
|
output voltage |
400 V 3 phases
|
|
Maximum configurable power in VA |
20000 VA
|
|
rated power in VA |
20000 VA
|
product certifications |
FCC part 15 class A
UL 1778 5th edition |
|
---|---|---|
standards |
CSA C22.2 No 107.3
EN/IEC 62040-1 EN/IEC 62040-2 EN/IEC 62040-3 IEC 60721-4-2 level 2M2 |
ambient air temperature for operation |
0…40 °C
|
|
---|---|---|
relative humidity |
0…95 % non-condensing
|
|
operating altitude |
0…3281 ft
|
|
ambient air temperature for storage |
-25…55 °C
|
|
storage altitude |
0.00…15240.00 m
|
|
acoustic level |
65 dBA
|
|
heat dissipation |
2187.8 Btu/h
|
|
show note OP temperature |
No
|
|
IP degree of protection |
IP21
|
battery type |
External battery system
|
|
---|---|---|
number of battery filled slots |
0
|
|
number of battery free slots |
0
|
|
liquid value |
0
|
|
battery voltage |
384…576 V DC
|
|
discharge battery voltage |
307 V DC
|
|
max current discharge |
68 A
|
|
battery curve |
B
|
|
Battery power in VAH |
0 VAh runtime
|
|
extended runtime |
0
|
free slots |
1
|
|
---|---|---|
control panel |
Touch screen LCD user interface
|
|
alarm |
Audible and visible alarms prioritized by severity
|
Package 1 Weight |
235 kg
|
|
---|---|---|
Package 1 Height |
168 cm
|
|
Package 1 width |
64 cm
|
|
Package 1 Length |
99 cm
|
Warranty |
1 year on-site repair or replace with factory authorized Start-Up
|
---|