[titles text=”T3VyJTIwVXNlcnM=” type=”h2″]






[titles text=”T3VyJTIwVXNlcnM=” type=”h2″]
Presentation |
Highly efficient, easy-to-deploy 20kW, 400V 3-phase UPS that brings best-in-class power protection and low total cost of ownership to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. This UPS is for up to 4 smart modular high capacity battery strings, but is supplied without batteries, so you can easily customize the battery runtime. Includes 5×8 start-up service.
|
|
---|---|---|
Lead time |
Usually Ships within 2 Weeks
|
provided equipment |
Dust filter
Installation manual Integrated network management Start-up service EcoStruxure Ready |
|
---|---|---|
Number of power module free slots |
0
|
|
Number of power module filled slots |
0
|
|
redundant |
No
|
|
UPS size |
WS
|
surface finish |
Gloss level 85%
|
|
---|---|---|
colour |
White (RAL 9003)
|
|
depth |
84.7 cm
|
|
height |
148.5 cm
|
|
mounting preference |
No preference
|
|
net weight |
200 kg
|
|
mounting mode |
Not rack-mountable
|
|
two post mountable |
0
|
|
USB compatible |
No
|
|
width |
52.1 cm
|
network frequency |
40…70 Hz
|
|
---|---|---|
input voltage limits |
340…460 V 400 V
|
|
inputvolt_other |
380 V
415 V |
|
maximum input current |
36 A
|
|
max short time withstand current |
65 kA
|
|
input harmonic distortion |
Less than 3 % for full load
|
|
input voltage |
400 V 3 phases
|
|
load power factor |
From 0.7 leading to 0.7 lagging without any derating
|
|
cos phi |
0.99
|
rated power in W |
20000 W
|
|
---|---|---|
Maximum configurable power in W |
20000 W
|
|
harmonic distortion |
Less than 3 %
|
|
output frequency |
50 Hz sync to mains
60 Hz sync to mains |
|
outputvolt_other |
380 V
415 V |
|
crest factor |
2.5
|
|
UPS type |
Double conversion online
|
|
Wave type |
Sine wave
|
|
output voltage tolerance |
+/- 5% after 2ms
+/-1% after 50ms |
|
output harmonic distortion |
< 1% linear load and < 3% non-linear load
|
|
output overload operation |
10 minutes at 125% and 60 seconds at 150%
|
|
bypass type |
Built-in static bypass
|
|
curve equation |
Efficiency
|
|
curve fixed loss |
0.0073
|
|
curve load maximum |
100 %
|
|
curve load minimum |
1 %
|
|
curve proportional loss |
0.0148
|
|
curve square loss |
0.013
|
|
curve X-axis maximum |
100 %
|
|
curve test cond ID |
Curve fit to measured efficiency data. All measurements taken in normal operating mode, at typical environmental conditions, with 400V 50Hz input and 400V 50Hz balanced resistive load (PF = 1.0) output.
|
|
curve X-axis minimum |
0 %
|
|
curve X-axis title |
Load
|
|
curve X-axis units |
Percentage
|
|
curve Y-axis maximum |
100 %
|
|
curve Y-axis minimum |
50 %
|
|
curve Y-axis title |
Efficiency
|
|
curve Y-axis units |
Percentage
|
|
graph display |
1
|
|
output voltage |
400 V 3 phases
|
|
Maximum configurable power in VA |
20000 VA
|
|
rated power in VA |
20000 VA
|
standards |
IEC 62040-1-1
IEC 62040-2 OSHPD |
---|
ambient air temperature for operation |
0…40 °C
|
|
---|---|---|
relative humidity |
0…95 % non-condensing
|
|
operating altitude |
0…3300 ft
|
|
ambient air temperature for storage |
-15…40 °C
|
|
Storage Relative Humidity |
Non-condensing 10…80 %
|
|
storage altitude |
0.00…3048.00 m
|
|
acoustic level |
55 dBA
|
|
heat dissipation |
2431 Btu/h
|
|
show note OP temperature |
No
|
|
IP degree of protection |
IP20
|
battery type |
VRLA
|
|
---|---|---|
number of battery filled slots |
0
|
|
number of battery free slots |
0
|
|
liquid value |
0
|
|
battery voltage |
480 V
|
|
discharge battery voltage |
384 V
|
|
max current discharge |
54 A
|
|
battery curve |
B
|
|
Battery power in VAH |
0 VAh runtime
|
|
extended runtime |
0
|
control panel |
Touch screen LCD user interface
|
|
---|---|---|
alarm |
Audible and visible alarms prioritized by severity
|
Package 1 Weight |
200 kg
|
|
---|---|---|
Package 1 Height |
168 cm
|
|
Package 1 width |
64 cm
|
|
Package 1 Length |
99 cm
|
Warranty |