Model |
Capacity at 270C when discharged at C20 up to 1.75 vpc (1.280 sp. gr) |
Dimension (+/-3mm) |
Weight
(Kg +/-5%) |
Volume of Electrolyte
(1.220 Sp. Gr) Liters |
Initial charge Minimum AH input (AH) |
Initial Charge of Constant Current (A) |
Constant Potential Limiting Current (Amps) |
Trickle Charge
(Current in mA) |
Length |
Width |
Height* |
Dry |
Filied |
Start (upto 2.36 vpc) |
Finish (upto 2.75 vpc) |
Min. |
Max. |
IT 400 |
110 Ah
|
506
|
220
|
257
|
29.10
|
43.35
|
11.40
|
450
|
12
|
6
|
25
|
100
|
400
|
IT 500 |
150 Ah
|
500
|
187
|
430
|
33.80
|
60.05
|
23.80
|
540
|
14.4
|
7.2
|
30
|
120
|
480
|
IT 550 |
165 Ah
|
500
|
187
|
430
|
35.80
|
60.80
|
20.00
|
610
|
16
|
8
|
34
|
135
|
540
|
IT 650 |
200 Ah
|
500
|
187
|
430
|
45.00
|
72.00
|
21.60
|
720
|
19.2
|
9.6
|
40
|
160
|
640
|
|
|
*At 270C when discharge at C20 upto 1.75 vpc
|
Higher Discharge Rates (Optional)
|
Hours |
|
10
|
5
|
3
|
1
|
Capacity Ah |
IT400 |
100
|
83
|
72
|
50
|
IT500 |
120
|
100
|
86
|
60
|
IT550 |
135
|
112
|
97
|
68
|
IT650 |
160
|
133
|
115
|
88
|
|
|
Initial Charging Instructions |
- Filling in Specific Gravity : 1.220 +/ – 0.005 at 27º C
- Rest Period : 10-12 hrs
- Minimum Ah input : 450 Ah for IT400, 540 Ah for IT500, 610 Ah for IT550 and 720 Ah for IT 650
- In order to reduce the charging time, the following routine may be adopted. For IT400, the initial charging current may be 12A upto 2.36vpc followed By 6A upto 2.75 vpc. For IT500, the initial charging current may be 14.4A upto 2.36vpc followed By 7.2A upto 2.75 vpc. For IT550, the initial charging current may be 16A upto 2.36vpc followed By 8A upto 2.75 vpc. For IT 650 , the initial charging current may be 19.2A Up to 2.36vpc followed by 9.6A upto 2.75vpc.However in both cases, minimum Ah to be given. Under the circumstances, Battery temperature should not exceed 50ºC. In case the temperature exceeds 50ºC Adequate rest to be given till the electrolyte temp. comes to ambient temp. and charging to be continued.
- Conditions of fully charged
- 3 consecutive hourly readings of specific gravity and voltage become constant
- Top of charge voltage will e around 16.2V – 16.5V.
- All cells should gas freely
- Minimum Ah has been given.
- Specified gravity of fully charged condition : 1.250 +/ – 0.005 at 27º
|
|
Normal Recharging Instruction |
Recharging through Inverter at constant potential mode of 14.4V with limited current as specified. After battery potential matches 14.4V, the battery should continue in trickle charge made at constant potential of 13.8V.
|
|
Statutory Notice |
All batteries contain lead, which is harmful for humans and environment. As per statutory requirements, the used battery must be returned to the authorized dealer, manufacturer or at the designated collection centres.
|