Our Users


Quick Quotation

Inva Flat



INVA FLAT 1800 & 2000

Advantages

Extra heavy duty thicker plates as per exclusive Exide design ensuring durability, resistance to corrosion and inbuilt margins for high ambient temperature.

 

Built with PE pocket type separator bonded with glass mat for extra support to active material, making the battery more suitable for deep cycle application.

There is high acid volume per ampere hour ensuring low maintenance characteristics.

Suitable for long and frequent powercuts with quick recharge adoptability

Substantial savings in floor area

Resistance to abuse

   

Technical Specification


Model


Capacity*


Dimension (+/-3mm)


Weight
(Kg +/-5%)


Volume of Electrolyte
(1.220 Sp. Gr) Liters/Cell


Initial charge Minimum AH input (AH)


Initial Charge of Constant Current (A)


Constant Potential Limiting Current (Amps)


Trickle Charge
(Current in mA)




Length




Width




Height*




Dry




Filied

Start (upto 2.36 vpc)

Finish (upto 2.75 vpc)




Min.




Max.

INVA FLAT 1800

180 Ah

500

187

430

36.50

62.50

3.55

525

18.0

9.0

37.50

150

600

INVA FLAT 2000

200 Ah

500

187

430

47.77

72.50

3.35

615

21.0

10.5

44.00

175

700

  

*The height mentioned is upto terminal top.

Higher Discharge Rates (Optional)

Hours

 

10

5

3

1

Capacity Ah

INVA FLAT1800

150

132

117

87

INVA FLAT2000

175

154

137

102

 
Initial Charging Instructions
  • Filling in Specific Gravity : 1.220 +/ - 0.005 at 27º C
  • Rest Period : 12 hrs
  • Minimum Ah input : 525Ah for IF1800 and 615Ah for IF2000
  • In order to reduce the charging time, the following routine may be adopted. For IF1800, the initial charging current may be 18A upto 2.36 vpc followed by 9A upto 2.75 vpc. For IF2000, the initial charging current may be 21A upto 2.36 vpc followed by 10.5A upto 2.75 vpc.

    However in both cases, minimum Ah input to be given. Under no circumstances, battery temperature should not exceed 500C. In case the temperature exceeds 500C, adequate rest to be given till the electrolyte temperature comes to ambient temperature and charging to be continued.
  • Conditions of fully charged
    • 3 consecutive hourly readings of specific gravity and voltage become constant
    • Top of charge voltage will be around 16.2V - 16.5V
    • All cells should gas freely
    • Minimum Ah has been given
  • Specified gravity of fully charged condition : 1.250 +/ - 0.005 at 27ºC

 
Normal Recharging Instructions

Recharging through Inverter at constant potential mode of 14.4V with limited current as specified. After battery potential reaches 14.4V, the battery should continue in float charge made at constant potential of 13.5V.

 

Statutory Notice